GMD: Khulna |
Sub-station: Satkhira 132/33 KV |
Sub-station Identification No. 30 |
|
Date: 20/10/2010 |
Reference File No. 27 |
|
|
Transformer: |
|
|
|
|
|
||||||||
|
ID No. |
Bank |
Rated Voltage (Kv) |
Capacity (MVA) |
OLTC |
Manufacturer |
Date of Commissioning |
Remarks |
||||||
|
T1 X-Former |
|
132±12x1.25%/33 |
25/41 |
MSI/II 301/302 245B 14273 WR |
MR REINHAUSEN, GERMANY |
18.11.2006 |
|
||||||
|
T2 |
|
132±12x1.25%/33 |
25/41 |
MSI/II 301/302 245B 14273 WR |
MR REINHAUSEN, GERMANY |
|
|
||||||
|
Circuit Breaker: |
|
|
|
|
|
||||||||
|
ID No. |
Name |
Type |
Rated Current [A] |
Rated fault Current [kA] |
Manufacturer |
Date of Commissioning |
Remarks |
||||||
|
152 B |
Khulna South – I C.B |
Hydraulic |
3150 |
|
Pingdingshan Tianying High Voltage Switchgear Co. |
18.112006 |
|
||||||
|
252 B |
Khulna South – II C.B |
Hydraulic |
3150 |
|
Pingdingshan Tianying High Voltage Switchgear Co. |
|
|
||||||
|
352 B |
T1 X-former. C.B |
Pneumatic |
2500 |
|
Shanghai Huatong Switchgear Works. |
18.11.2006 |
|
||||||
|
452 B |
T2 X-former C.B |
Pneumatic |
2500 |
|
Shanghai Huatong Switchgear Works. |
|
|
||||||
|
552 B |
Bus Couper C.B |
Hydraulic |
3150 |
|
Pingdingshan Tianying High Voltage Switchgear Co. |
|
|
||||||
|
Disconnector: |
|
|
|
|
|
||||||||
|
ID No. |
Name |
Rated Current [A] |
Hand / Motor Operated |
Manufacturer |
Date of Commissioning |
Remarks |
|
||||||
|
189E |
Line Khulna South-I Earth DS. |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
18.11.2006 |
|
|
||||||
|
189L |
Line Khulna South-I |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
18.11.2006 |
|
|
||||||
|
189A |
Line Khulna South-I Bus A |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
18.11.2006 |
|
|
||||||
|
189B |
Line Khulna South-I Bus B |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
289E |
Line Khulna South-II Earth DS. |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
289L |
Line Khulna South-II |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
289A |
Line Khulna South-I Bus A |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
289B |
Line Khulna South-I Bus B |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
589A |
Bus Coupler Bus A |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
589B |
Bus Coupler Bus B |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
389A |
T1 Bus A DS |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
18.11.2006 |
|
|
||||||
|
389B |
T1 Bus B DS |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
489A |
T2 Bus A DS |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
489B |
T2 Bus B DS |
1250 |
Both |
Shanghai Huatong Switchgear Project Co. Ltd. |
|
|
|
||||||
|
Bus Bar: |
|
|
|
|
|
||||||||
|
ID No. |
Rated Voltage |
Conductor Type |
Rated Current [A] |
Bus Scheme |
No. of Sections |
Date of Commissioning |
Remarks |
||||||
|
Bus Bar A |
132 KV |
|
1250 A |
|
1 |
18.11.2006 |
|
||||||
|
Bus Bar B |
132 KV |
|
1250 A |
|
1 |
18.11.2006 |
|
||||||
|
Shunt Capacitor: |
|
|
|
|
|
||||||||
|
ID No. |
Name |
Rated Voltage (Kv) |
Capacity (MVAR) |
Manufacturer |
Date of Commissioning |
Remarks |
|
||||||
|
Lightning Arrestor: |
|
|
|
|
|
||||||||
|
ID No. |
Name of Feeder |
Type |
Rated Voltage (Kv) |
Manufacturer |
Date of Commissioning |
Remarks |
|
||||||
|
Line Khulna South-I LA |
|
Y10W1-120/293 |
132 |
Fushan Huatai Electric Porcelain & Electrical Manufacturing Co., Ltd |
18.11.2006 |
|
|
||||||
|
Line Khulna South-II LA |
|
Y10W1-120/293 |
132 |
Fushan Huatai Electric Porcelain & Electrical Manufacturing Co., Ltd |
|
|
|
||||||
|
T1 LA |
|
Y10W1-120/293 |
132 |
Fushan Huatai Electric Porcelain & Electrical Manufacturing Co., Ltd |
|
|
|
||||||
|
T2 LA |
|
Y10W1-120/293 |
132 |
Fushan Huatai Electric Porcelain & Electrical Manufacturing Co., Ltd |
|
|
|
||||||
|
Protective Relay: |
|
|
|
|
|
||||||||
|
ID No. |
Name |
Objective |
Type |
|
Manufacturer |
Date of Commissioning |
Remarks |
||||||
|
Relay-1 |
Line Khulna South-I Distance Relay |
Distance Relay |
|
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-2 |
Line Khulna South-I OC/EF Relay |
Over Current Earth Fault Relay |
50 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-3 |
Line Khulna South-I Voltage Relay |
Voltage Relay |
YJ-27 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-4 |
Line Khulna South-II Distance Relay |
Distance Relay |
|
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-5 |
Line Khulna South-II OC/EF Relay |
Over Current & Earth Fault Relay |
50 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-6 |
Line Khulna South-II Voltage Relay |
Voltage Relay |
YJ-27 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-7 |
T1 –Differential Relay |
Differential Relay |
87 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-8 |
T1 – Over Current & Earth Fault Relay |
Over Current & Earth Fault Relay |
50/51, 50N/51N |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-9 |
T1 Transformer Neutral Relay. |
Transformer Neutral Relay |
51N |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-10 |
T1 Time Relay |
Time Relay |
SJ |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-11 |
T1 Voltage Relay |
Voltage Relay |
YJ-59 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-12 |
T1 Over Current Relay (OLTC) |
Over Current Relay |
KCL |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-13 |
T1 Over Current Relay (Fan) |
Over Current Relay |
KCL |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-14 |
T2 – Over Current & Earth Fault Relay |
Over Current & Earth Fault Relay |
50/51, 50N/51N |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-15 |
T2 – Over Current & Earth Fault Relay |
Over Current & Earth Fault Relay |
50/51, 50N/51N |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-16 |
T2 Transformer Neutral Relay. |
Transformer Neutral Relay |
51N |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-17 |
T2 Time Relay |
Time Relay |
SJ |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-18 |
T2 Voltage Relay |
Voltage Relay |
YJ-59 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-19 |
T2 Over Current Relay (OLTC) |
Over Current Relay |
KCL |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-20 |
T2 Over Current Relay (Fan) |
Over Current Relay |
KCL |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-21 |
Bus Coupler-Over Current & Earth Fault Relay |
Over Current & Earth Fault Relay |
50 |
|
AREVA |
18.11.2006 |
|
||||||
|
Relay-22 |
Bus Coupler- SYN. Relay |
Syn. Relay |
|
|
AREVA |
18.11.2006 |
|
||||||
|
Meters: |
|
|
|
|
|
||||||||
|
ID No. |
Name |
Purpose |
Type |
Manufacturer |
Date of Commissioning |
Remarks |
|
||||||
|
200504x033U0010 |
Line Khulna South-I |
Taking Import Power Reading. |
Digital Meter |
CHANGSHA WE I SHENG ELECTRONICS CO., LTD. |
18.11.2006 |
|
|
||||||
|
200504x033U0008 |
Line Khulna South-II |
Taking Import Power Reading |
Digital Meter |
CHANGSHA WE I SHENG ELECTRONICS CO., LTD |
18.11.2006 |
|
|
||||||
|
200504x033U0006 |
T1 Transformer |
|
Digital Meter |
CHANGSHA WE I SHENG ELECTRONICS CO., LTD |
18.11.2006 |
|
|
||||||
|
200504x033U0005 |
T2 Transformer |
|
Digital Meter |
CHANGSHA WE I SHENG ELECTRONICS CO., LTD |
18.11.2006 |
|
|
||||||
|
Auxiliary Equipment: |
|
|
|
|
|
||||||||
|
ID No. |
Name |
Type of Facility |
|
|
Manufacturer |
Date of Commissioning |
Remarks |
||||||
|
T41 |
Transformer |
Supplying Power to the Sub-station. |
Dyn-11 |
|
|
|
|
||||||
|
T42 |
Transformer |
Supplying Power to the Dormatory. |
Dyn-11 |
|
|
|
|
||||||
|
Battery: |
|
|
|
|
|
||||||||
|
ID No. |
Name |
|
|
|
Manufacturer |
Date of Commissioning |
Remarks |
||||||
|
Battery-1 |
Nical-Cadmium Battery |
|
|
|
Xinxiang Taihang Power Source Co. Ltd |
18.11.2006 |
|
||||||
|
Battery-2 |
Nical-Cadmium Battery |
|
|
|
Xinxiang Taihang Power Source Co. Ltd |
18.11.2006 |
|
||||||
|
Battery Charger: |
|
|
|
|
|
||||||||
|
ID No. |
|
|
|
|
Manufacturer |
Date of Commissioning |
Remarks |
||||||
|
Charger -1 |
Charger set 1 |
|
|
|
Shanghai Glen Intelligent Electric Co. Ltd |
18.11.2006 |
|
||||||
|
Charger-2 |
Charger set 2 |
|
|
|
Shanghai Glen Intelligent Electric Co. Ltd |
18.11.2006 |
|
||||||
|
Transmission Line:
|
|
|
|
|
|
||||||||
|
ID No. |
Name |
Circuit |
Length in km (Route/Circuit) |
No of Tower |
Conductor Type & Cross section area (mm2) |
Date of Commissioning |
Remarks |
||||||
|
Line-1 |
Line Khulna South-I |
Singel |
44 |
1 |
164 |
636 MCM AAAC |
18.11.2006 |
|
|||||
|
Substation Land: |
|
|
|
|
|
||||||||
|
Area |
Mouza |
CS Daag No. |
RS Daag No. |
Khatiyan No. |
|
|
Remarks |
||||||
|
3.34 Acre |
|
|
|
|
|
|
|
||||||
|
Control Room Building: |
|
|
|
|
|
||||||||
|
No. of Building |
Objective |
Single/ Multi storied |
Area in each floor (sq. ft.) |
Total Area (sq. ft.) |
|
|
Remarks |
||||||
|
Home About Us Vision/mission Directions Contact us Info Blog Important Links At A Glance Equipment Information Gallery Chatting Demand & Distribution Facility Records |
|||||
|